Controlling System Voltage Controlling System Voltage Without capacitors, the voltage drop across a system is:
or
Vd = voltage drop across system leading to the load kVA = 3-phase load kVA kV = phase to phase voltage at load cos theta = cosine of the power factor angle R = resistance of system leading up to the load (ohms) X = inductive reactance of the system leading up to the load (ohms) The percent voltage rise at a load due to the addition of a capacitor bank is: Vr = % voltage rise at load kVAR = 3-phase capacitive kilovar kV = phase to phase kilovolts X = inductive reactance of the system KVAsc = 3-phase short circuit kVA The percent voltage rise from primary to secondary of a transformer is:
Where: Vr = the percent voltage rise at the transformer kVAR = 3-phase kilovar applied kVAt = 3-phase kVA of the transformer Xt = transformer reactance in percent |
|
|||